NOVA 110

Performance
Nominal COP (Ambient temperature 7 °C, Fwd, RTN 30 °C) 3.73
SCOP (application at low temperature 35°C) 4.19
SCOP (application at average temperature 55°C) 3.68
Capacity range (min-max) 45-110 kW
Operating range
Ambient temperature (air) -20°C to 35°C
Forward temperature (heating circuit) 35°C to 70°C
Sound
Sound pressure level at 10 m 42.0 dB(A)
Refrigerant
Type R290 (propane)
Global warming potential (GWP) 0.02
Ozone-depleting potential (ODP) 0
Load 1x8 kg
Dimensions and weight
Length (excl. electrical cabinet) 2.40 m
Width 1.54 m
Height (without levelling shoes) 2.44 m
Dry weight 1177 kg
Electric
Nutrition 3 ph / 400 V (+N+PE) / 50 hZ
Fuse protection 63 A
Heating circuit
supply and return connections 1 ½" nipple
Communications
Internet 4G (SIM card incl.) or RJ45 option
Modbus-RTU RS485

NOVA 220

Performance
Nominal COP (Ambient temperature 7 °C, Fwd, RTN 30 °C) 3.93
SCOP (application at low temperature 35°C) 4.19
SCOP (application at average temperature 55°C) 3.68
Capacity range (min-max) 45 - 220 kW
Operating range
Ambient temperature (air) -20°C to 35°C
Forward temperature (heating circuit) 35°C to 70°C
Sound
Sound pressure level at 10 m 45.0 dB(A)
Refrigerant
Type R290 (propane)
Global warming potential (GWP) 0.02
Ozone-depleting potential (ODP) 0
Load 2x8 kg
Dimensions and weight
Length (excl. electrical cabinet) 4.80 m
Width 1.54 m
Height (without levelling shoes) 2.44 m
Dry weight 2419 kg
Electric
Nutrition 3 ph / 400 V (+N+PE) / 50 hZ
Fuse protection 150 A
Heating circuit
supply and return connections Ø76.1 mm
Communications
Internet 4G (SIM card incl.) or RJ45 option
Modbus-RTU RS485

NOVA 330

Performance
Nominal COP (Ambient temperature 7 °C, Fwd, RTN 30 °C) 4.01
SCOP (application at low temperature 35°C) 4.19
SCOP (application at average temperature 55°C) 3.68
Capacity range (min-max) 45 - 330 kW
Operating range
Ambient temperature (air) -20°C to 35°C
Forward temperature (heating circuit) 35°C to 70°C
Sound
Sound pressure level at 10 m 46.8 dB(A)
Refrigerant
Type R290 (propane)
Global warming potential (GWP) 0.02
Ozone-depleting potential (ODP) 0
Load 3x8 kg
Dimensions and weight
Length (excl. electrical cabinet) 7.20 m
Width 1.54 m
Height (without levelling shoes) 2.44 m
Dry weight 3568 kg
Electric
Nutrition 3 ph / 400 V (+N+PE) / 50 hZ
Fuse protection 200 A
Heating circuit
supply and return connections Ø76.1 mm
Communications
Internet 4G (SIM card incl.) or RJ45 option
Modbus-RTU RS485

NOVA 440

Performance
Nominal COP (Ambient temperature 7 °C, Fwd, RTN 30 °C) 4.04
SCOP (application at low temperature 35°C) 4.19
SCOP (application at average temperature 55°C) 3.68
Capacity range (min-max) 45 - 440 kW
Operating range
Ambient temperature (air) -20°C to 35°C
Forward temperature (heating circuit) 35°C to 70°C
Sound
Sound pressure level at 10 m 48.0 dB(A)
Refrigerant
Type R290 (propane)
Global warming potential (GWP) 0.02
Ozone-depleting potential (ODP) 0
Load 4x8 kg
Dimensions and weight
Length (excl. electrical cabinet) 9.6 m
Width 1.54 m
Height (without levelling shoes) 2.44 m
Dry weight 4698 kg
Electric
Nutrition 3 ph / 400 V (+N+PE) / 50 hZ
Fuse protection 250 A
Heating circuit
supply and return connections Ø76.1 mm
Communications
Internet 4G (SIM card incl.) or RJ45 option
Modbus-RTU RS485