Nova Series
Best-in-class modular heat pump
The design of the Nova Series is based on an uncompromising commitment to high performance and quality.
Since 2019, our pioneering air-water modular heat pump system has become the go-to solution for a wide variety of Nordic commercial and light industrial end-users.
The Nova Series is now available in the Benelux.
Features
Uncompromising quality
Our Nova Series heat pump system is built from carefully selected quality components and designed for optimal thermodynamic performance.
Overheating control
X
Low superheat control method to optimise evaporator surface area, resulting in higher COP.
6-cylinder engine
X
Semi-hermetic, gas-cooled reciprocating compressor with variable speed control.
Triple heat transfer
X
Unique triple heat transfer concept for higher COP results.
Superior performance
Excellent thermodynamic efficiency for maximum energy savings.
Flexible Plug & Play solution
Designed for easy installation and light maintenance.
Built-in quality
Sustainably built with first-class craftsmanship, high-quality components and Scandinavian heat pump know-how.
The Nova Series is robust and durable and has been tested during many long and harsh Scandinavian winters.
Scalable modular system
A range of customisable configurations possible with capacities from 45 kW to 1320 kW.
Compact design
Small physical footprint designed with close urban constraints in mind.
Natural refrigerant R290 (propane)
Excellent performance with ultra-low environmental impact (GWP 0.02).
Technical specifications
Nova Series overview
Model selection:
| Performance | Nominal COP (Ambient temperature 7 °C, Fwd, RTN 30 °C) | 3.73 |
|---|---|
| SCOP (application at low temperature 35°C) | 4.19 |
| SCOP (application at average temperature 55°C) | 3.68 |
| Capacity range (min-max) | 45-110 kW |
| Operating range | Ambient temperature (air) | -20°C to 35°C |
|---|---|
| Forward temperature (heating circuit) | 35°C to 70°C |
| Sound | Sound pressure level at 10 m | 42.0 dB(A) |
|---|
| Refrigerant | Type | R290 (propane) |
|---|---|
| Global warming potential (GWP) | 0.02 |
| Ozone-depleting potential (ODP) | 0 |
| Load | 1x8 kg |
| Dimensions and weight | Length (excl. electrical cabinet) | 2.40 m |
|---|---|
| Width | 1.54 m |
| Height (without levelling shoes) | 2.44 m |
| Dry weight | 1177 kg |
| Electric | Nutrition | 3 ph / 400 V (+N+PE) / 50 hZ |
|---|---|
| Fuse protection | 63 A |
| Heating circuit | supply and return connections | 1 ½" nipple |
|---|
| Communications | Internet | 4G (SIM card incl.) or RJ45 option |
|---|---|
| Modbus-RTU | RS485 |
| Performance | Nominal COP (Ambient temperature 7 °C, Fwd, RTN 30 °C) | 3.93 |
|---|---|
| SCOP (application at low temperature 35°C) | 4.19 |
| SCOP (application at average temperature 55°C) | 3.68 |
| Capacity range (min-max) | 45 - 220 kW |
| Operating range | Ambient temperature (air) | -20°C to 35°C |
|---|---|
| Forward temperature (heating circuit) | 35°C to 70°C |
| Sound | Sound pressure level at 10 m | 45.0 dB(A) |
|---|
| Refrigerant | Type | R290 (propane) |
|---|---|
| Global warming potential (GWP) | 0.02 |
| Ozone-depleting potential (ODP) | 0 |
| Load | 2x8 kg |
| Dimensions and weight | Length (excl. electrical cabinet) | 4.80 m |
|---|---|
| Width | 1.54 m |
| Height (without levelling shoes) | 2.44 m |
| Dry weight | 2419 kg |
| Electric | Nutrition | 3 ph / 400 V (+N+PE) / 50 hZ |
|---|---|
| Fuse protection | 150 A |
| Heating circuit | supply and return connections | Ø76.1 mm |
|---|
| Communications | Internet | 4G (SIM card incl.) or RJ45 option |
|---|---|
| Modbus-RTU | RS485 |
| Performance | Nominal COP (Ambient temperature 7 °C, Fwd, RTN 30 °C) | 4.01 |
|---|---|
| SCOP (application at low temperature 35°C) | 4.19 |
| SCOP (application at average temperature 55°C) | 3.68 |
| Capacity range (min-max) | 45 - 330 kW |
| Operating range | Ambient temperature (air) | -20°C to 35°C |
|---|---|
| Forward temperature (heating circuit) | 35°C to 70°C |
| Sound | Sound pressure level at 10 m | 46.8 dB(A) |
|---|
| Refrigerant | Type | R290 (propane) |
|---|---|
| Global warming potential (GWP) | 0.02 |
| Ozone-depleting potential (ODP) | 0 |
| Load | 3x8 kg |
| Dimensions and weight | Length (excl. electrical cabinet) | 7.20 m |
|---|---|
| Width | 1.54 m |
| Height (without levelling shoes) | 2.44 m |
| Dry weight | 3568 kg |
| Electric | Nutrition | 3 ph / 400 V (+N+PE) / 50 hZ |
|---|---|
| Fuse protection | 200 A |
| Heating circuit | supply and return connections | Ø76.1 mm |
|---|
| Communications | Internet | 4G (SIM card incl.) or RJ45 option |
|---|---|
| Modbus-RTU | RS485 |
| Performance | Nominal COP (Ambient temperature 7 °C, Fwd, RTN 30 °C) | 4.04 |
|---|---|
| SCOP (application at low temperature 35°C) | 4.19 |
| SCOP (application at average temperature 55°C) | 3.68 |
| Capacity range (min-max) | 45 - 440 kW |
| Operating range | Ambient temperature (air) | -20°C to 35°C |
|---|---|
| Forward temperature (heating circuit) | 35°C to 70°C |
| Sound | Sound pressure level at 10 m | 48.0 dB(A) |
|---|
| Refrigerant | Type | R290 (propane) |
|---|---|
| Global warming potential (GWP) | 0.02 |
| Ozone-depleting potential (ODP) | 0 |
| Load | 4x8 kg |
| Dimensions and weight | Length (excl. electrical cabinet) | 9.6 m |
|---|---|
| Width | 1.54 m |
| Height (without levelling shoes) | 2.44 m |
| Dry weight | 4698 kg |
| Electric | Nutrition | 3 ph / 400 V (+N+PE) / 50 hZ |
|---|---|
| Fuse protection | 250 A |
| Heating circuit | supply and return connections | Ø76.1 mm |
|---|
| Communications | Internet | 4G (SIM card incl.) or RJ45 option |
|---|---|
| Modbus-RTU | RS485 |